EMO T*
High performance thermoelectric actuator – For ON/OFF or PWM control
Used in conjunction with small terminal valves e.g. TBV-C and TA-Nano, the high performing EMO T* actuator offers reliable on/ off control and a high enclosure class. The position indicator is visible from all sides and allows easy maintenance procedures. The snap-on and First-open functions facilitate the installation and commissioning of the EMO T*.
Product branding

Features and Benefits
High adjusting force and high reliability
Tested in conjunction with all of IMI valves up to 150 000 cycles.
High enclosure class IP54
For secure operations at any installation positions.
Position indicator visible from all sides
For straightforward maintenance.
Low power consumption
For reduced energy consumption and easy power supply dimensioning.
M30x1.5 snap-on ring
Facilitating installation of actuator on valve thread.
Applications
Designed for ON/OFF or PWM control.
Temperature
Max. ambient temperature: 60°C
Max. medium temperature: 100°C
Min. ambient temperature: 0°C
Storage temperature: -25°C to +60°C
Supply voltage
24 VAC/VDC +25% / -20% 230 VAC ±10% 120 VAC ±10% Frequency 50-60 Hz
Power consumption
24 V:
During operation ≤ 1 W (VA)
Starting current ≤ 300 mA during max. 2 min.
230 V:
During operation ≤ 1 W (VA)
Starting current ≤ 550 mA during max. 100 ms.
Stroke
5 mm
Valve position visible due to position indicator.
Operating cycle time
~ 4 min when starting from cold.
Adjusting force
100 N +10%
Connection to valve
M30x1,5 plastic snap-on ring.
Cable
Cable length: 1 m, 2 m or 5 m.
For longer cable please order a plug-in cable from the accessory section.
Connection cable: 2 x 0,75 mm2. The cable is stripped 100 mm and each wire is stripped 8 mm.
Halogen free as option, fire class B2ca – s1a, d1, a1 according to EN 50575.
Material
Shock-resistant Polyamide, white RAL 9016.
Ingress protection
IP54 at any position.
Protection class
III, EN 60730
Certifications and directives
CE, EN 60730-2-14