Compresso Connect
For heating systems up to 12 MW and cooling systems up to 18 MW
Compresso is a precision pressurisation system with compressors for heating, solar and chilled water systems. It is especially suitable in situations where compactness and precision are required. The system capacity range lies between pressurisation with Statico and Transfero.The new BrainCube Connect control panel allows a new level of connectivity, enabling communication with the BMS system, other BrainCubes as well as remote operation of the pressurisation system through live viewing.
Product branding
Features and Benefits
Improved design for easier and more comfortable operation
Resistant 3.5" TFT illuminated colour touch display. Intuitive and user friendly menu. Web based interface with remote control and live view. BrainCube Connect control panel integrated into TecBox.
Remote Access and Trouble-shooting
Remote access and commissioning support, reducing the need for high skilled staff to perform operations. Quicker response time, reduced repair costs. Data logging for system performance checks.
State-of-the-Art Connectivity
Standardised connections to BMS and remote devices available (RS485, Ethernet, USB) enabling time savings during set-up and service and unit controllability. Communication with up to 12 BrainCubes in a Master/Slave network.
Applications
For systems according to EN 12828, SWKI HE301-01, solar systems according to EN 12976, ENV 12977, with on-site excess temperature protection in case of power outage.
Heating, solar and chilled water systems.
Temperature
Max. admissible ambient temperature, TA: 40°C
Min. admissible ambient temperature, TAmin: 5°C
Accuracy
Precision pressure maintenance ±0,1 bar
Electric load
See Articles
Supply voltage [V]
Compresso C10: 1 x 230 V (-6% + 10%), 50/60 Hz, Compresso C15: 1 x 230 V (-6% + 10%), 50 Hz
Transportation and storage
In frostless, dry places
Pressure
Max. admissible pressure, PS: see Articles
Min. admissible pressure, PSmin: 0 bar
Standard
Constructed according to MD 2006/42/EC, Annex II 1.A EMC-D. 2014/30/EU
Enclosure class
IP 22 according to EN 60529
For PED purposes
Min. admissible temperature, TSmin: -10°C
Max. admissible temperature, TS: 120°C
Material
Airproof butyl bag according to EN 13831.
Expansion vessel
Only together with Control unit TecBox. See Applications under Technical description - Control unit TecBox.
Art. No. |
---|