KTM 512
Product branding

Features and Benefits
Inline design
Inline flow allows high pressure drops without noise.
Adjustable flow
Ensures the design flow.
Adapters
For use with most available actuators.
Applications
Heating and cooling systems.
Functions
Control EQM: DN 15 low flow, DN 10-200 normal flow
Differential pressure control
Isolation (for use during system maintenance – see "Leakage rate")
Measuring (ΔH, t, q)
Pre-setting (max. flow)
Dimensions
DN 15-125
Pressure class [PN]
PN 16
PN 25
Differential pressure (ΔpV)
1600 kPa = 16 bar (ΔHmax)
Min. differential pressure:
Low flow (LF): 24 kPa (ΔHmin)
Normal flow (NF): 40 kPa (ΔHmin)
High flow (HF): 80 kPa (ΔHmin)
(Valid for max. position, fully open. Other positions will require lower differential pressure, check with the software HySelect.),
Flow range
DN 15/20 (LF): 120-800 l/h
DN 15/20 (NF): 150-1000 l/h
DN 15/20 (HF): 210 -1400 l/h
DN 25/32 (LF): 480 - 3200 l/h
DN 25/32 (NF): 570 - 3800 l/h
DN 25/32 (HF): 810 - 5400 l/h
DN 40/50 (LF): 1140 - 7600 l/h
DN 40/50 (NF): 1400 - 9500 l/h
DN 40/50 (HF): 1900 - 12600 l/h
DN 65 (LF): 2300-15400 l/h
DN 65 (NF): 3240-21600 l/h
DN 65 (HF): 4440 - 29600 l/h
DN 80 (LF): 2500 - 16700 l/h
DN 80 (NF): 3400 - 22700 l/h
DN 80 (HF): 4900 - 32500 l/h
DN 100 (LF): 4000 - 26600 l/h
DN 100 (NF): 6200 - 41200 l/h
DN 100 (HF): 7500 - 50600 l/h
DN 125 (LF): 5350 - 35600 l/h
DN 125 (NF): 8200 - 54900 l/h
DN 125 (HF): 10000 - 66800 l/h
qmax = l/h at each setting and fully open valve plug
Temperature
Max. working temperature: with measuring points: 120°C, without measuring points: 150°C
Min. working temperature: -10°C
Media
Water or neutral fluids, water-glycol mixtures (0-57%).
Characteristics
Indicative shaped EQM, best suited for modulating control
Leakage rate
Tight sealing
Actuators
*) Adapter 52 757-907 needed.
DN 100 LF: TA-Slider 750*
DN 100 NF/HF: TA-Slider 1600*
DN 125: TA-Slider 1600*
DN 15-50: TA-Slider 500
DN 65: TA-Slider 750*
DN 80 HF: TA-Slider 1600*
DN 80 LF/NF: TA-Slider 750*
Marking
IMI TA, DN, PN, Kvs, material and flow direction arrow
Connection
DN 15-50: External threads according to ISO 228.
DN 65-125: Flanges according to EN-1092-2, type 21. Face to face length according to EN 558 series 1.
Material
Valve insert: Brass
Throttle plug: Stainless steel
Valve plug: Stainless steel
Valve seat: Stainless steel
Seat seal: EPDM
Spindle: Stainless steel
Δp insert: Stainless steel (plastic components for DN 15-50)
Δp seat: Ryton plastic
Springs: Stainless steel,
Surface treatment
Electrophoretic painting.
The table below assists you in finding the relevant product based on its variant. For more details, please download the datasheet above.
Art. No. |
---|