Simply Vento
For heating systems
Simply Vento is a cyclonic vacuum degasser for heating systems. Through the process of rotating the water in a special cyclonic vacuum vessel, the gases are separated completely from the water. Its use is particularly recommended where performance, compact design and precision are required. The BrainCube Connect control panel allows a new level of connectivity, enabling communication with the BMS system, other BrainCubes as well as remote operation of the pressurisation system through live viewing.
Features and Benefits
Higher Efficiency Cyclonic vacuum degassing
Significantly higher efficiency than most other vacuum degassing systems.
Compact design for floor and wall hanging installation
Easy Commissioning, Remote Access and Trouble-shooting
Integrated standard connections to our IMI Webserver and to BMS.
Optional sound absorbing wall bracket
For Vento Compact in installations particularly sensitive to structure-borne sound.
Plug & Play installation and start-up
Connect unit to the installation
Plug in power supply
Follow the instructions displayed on the BrainCube
– Control unit TecBox
Applications
For systems according to EN 12828, SWKI HE301-01, EN 12976, ENV 12977, EN 12952, EN 12953
Heating systems.
Supply voltage [V]
1 x 230 V (± 10 %) / 50 Hz
Transportation and storage
In frostless, dry places
Media
Ethylene or propylene glycol-based antifreeze up to 50%.
Non-aggressive and non-toxic system media.
Pressure
Max. admissible pressure, PS: 10 bar
Min. admissible pressure, PSmin: -1 bar
Standard
Constructed according to LV-D. 2014/35/EU, EMC-D. 2014/30/EU
Temperature
Max. admissible temperature, TS: 90°C
Min. admissible temperature, TSmin: 0 °C
Max. admissible ambient temperature, TA: 40°C
Min. admissible ambient temperature, TAmin: 0°C
Enclosure class
IP54 according to EN 60529
Mechanical connections
Sin1: inlet from the system G1/2"
Sout: outlet to the system G1/2"
Material
Metal components with medium contact: carbon steel, cast iron, stainless steel, AMETAL®, brass, gunmetal.
Electrical connection
Onsite fuses according to power demand and local norms
3 potential-free outputs (NO) for external alarm indication (230V max. 2A)
1 RS 485 In/Output
1 Ethernet RJ45 plug socket
1 USB Hub plug socket