Skip to main content
TA-Slider 160 Fail-safe

TA-Slider 160 Fail-safe

Digitally configurable proportional push actuator with electronic fail-safe function – 160/200 N

Digitally configurable fail-safe actuators with or without change-over, and a wide range of setup options provide extensive flexibility for on-site parameter adaptation. Fully programmable binary input, relay and adjustable max. stroke of the valve bring new opportunities for advanced hydronic control and balancing.

Technical SpecificationsTA-Slider_160_Fail-safe_EN_low.pdf

Product branding

imi_ta

Features and Benefits

Fully configurable fail-safe

Setting of stroke position (extended, retracted or intermediate position) and delay feature for entering/leaving fail-safe mode for a reliable and optimal fail-safe function.

Convenient, reliable setup

Fully customisable by smartphone via Bluetooth using a TA-Dongle.

Fully configurable

More than 200 setup options allow input and output signals, binary input, relay, characteristics and many other parameters to be configured.

Easy diagnostics

Tracks the last 10 errors to allow system faults to be found quickly and health check of fail-safe function.

Quick copying of settings

Setup configuration can be copied quickly from the TA-Dongle to identical TA-Slider actuators.

Functions

Delayed start-up

Diagnostic/Logging

Electronic fail-safe function

Manual override (TA-Dongle)

Minimum stroke setting

Mode, status and position indication

Proportional control

Self-adjusting force

Stroke detection

Stroke limitation setting

Valve blockage protection

Valve clogging detection

Temperature

Max. medium temperature: 120°C

Operating environment: 0°C – +50°C (5-95%RH, non-condensing)

Storage environment: -20°C – +50°C (5-95%RH, non-condensing)

Control speed

10 s/mm

Supply voltage [V]

24 VAC/VDC ±15%. Frequency 50/60 Hz ±3 Hz

Power consumption

Peak: < 6.6 VA (VAC); < 3.2 W (VDC)

Operation: < 2.0 VA (VAC); < 0.9 W (VDC)

Standby: < 1.4 VA (VAC); < 0.45 W (VDC)

Peak consumption occurs for a short period after a power cut for recharging capacitors.

Input signal

0(2)-10 VDC, Ri 47 kΩ.

0.33 Hz low pass filter.

Adjustable hysteresis sensitivity 0.1-0.5 VDC.

Default setting: Proportional 0-10 VDC

Proportional: 0-10, 10-0, 2-10 or 10-2 VDC.

Proportional dual-range (for change-over): 0-3.3 / 6.7-10 VDC, 2-4.7 / 7.3-10 VDC, 0-4.5 / 5.5-10 VDC or 2-5.5 / 6.5-10 VDC.

Proportional split-range: 0-5, 5-0, 5-10 or 10-5 VDC; 0-4.5, 4.5-0, 5.5-10 or 10-5.5 VDC; 2-6, 6-2, 6-10 or 10-6 VDC.

Output signal

0(2)-10 VDC, max. 8 mA, min. 1.25 kΩ.

Default setting: Proportional 0-10 VDC

Ranges: See “Input signal”.

Stroke

6,9 mm

Automatic detection of the valve lift (stroke detection)

Noise level

Max. 30 dBA

Marking

Label: IMI TA, CE, product name, article No. and technical specification.


Colour

White RAL 9016, grey RAL 7047.

Adjusting force

160/200 N

Self-adjusting for IMI valves.

Connection to valve

Swivelling nut M30x1,5

Cable

1, 2 or 5 m.

Halogen free with wire end sleeves.

Fire class B2ca – s1a, d1, a1 according to EN 50575.

Type LiYY, 5x0.25 mm2.

Relay cable (R24 version):

1, 2 or 5 m.

Halogen free with wire end sleeves.

Fire class B2ca – s1a, d1, a1 according to EN 50575.

Type LiYY, 3x0.34 mm2.

Material

Cover: PC/ABS GF8

Housing: PA GF40.

Swivelling nut: Nickel-plated brass.

Ingress protection

IP54 all directions (according to EN 60529)

Protection class

III (SELV)

(according to EN 61140)

Certifications and directives

EMC-D. 2014/30/EU: EN 60730-1, -2-14.

LV-D. 2014/35/EU: EN 60730-1, -2-14.

RoHS-D. 2011/65/EU: EN 63000

The table below assists you in finding the relevant product based on its variant. For more details, please download the datasheet above.

Related products