Transfero TI Connect
Product branding

Features and Benefits
Applications
For systems according to EN 12828, SWKI HE301-01, EN 12976, ENV 12977, EN 12952, EN 12953
For systems to EN 12828 and optional >110 °C to EN 12952
Heating, solar and chilled water systems.
Pressure
Max. admissible pressure, PS: see Articles
Min. admissible pressure, PSmin: 0 bar
Temperature
Max. admissible temperature, TS: 90°C
Min. admissible temperature, TSmin: 0 °C
Max. admissible ambient temperature, TA: 40°C
Min. admissible ambient temperature, TAmin: 5°C
Media
According to VDI 2035 for non-aggressive and non-toxic system media.
Ethylene or propylene glycol-based antifreeze up to 50%.
Supply voltage [V]
Main current: 3x 400V / 50Hz (3P + PE); Control voltage: 230V / 50Hz (P + N + PE)
Accuracy
accuracy_02_bar
Expansion vessel
Only together with Control unit TecBox. See Applications under Technical description - Control unit TecBox.
Standard
Constructed according to PED 2014/68/EU.
Mechanical connections
Connection vessel (Sv): 80/6 DN/PN
Water make-up (Swm): Rp3/4
Electrical connection
4 potential free outputs ((individual parameterizable) for external message display (230V max. 2A),
2 potential-free outputs for status messages,
Motor circuit breakers of pump P1 and P2,
1 potential-free output for controlling an external water make-up device,
3 Grinding terminals for e.B. for optional pressure-, level-, temperature limiter.
1 RS 485 In/Output,
1 Ethernet RJ45 plug socket,
Terminal strip in PowerCube for direct wiring of the above-mentioned connectors,
1 USB Hub plug socket,
Software upgrade and LOG File Download.
Material
In essence: steel, brass and bronze
Enclosure class
IP 54
Warranty
5-year warranty for the airproof butyl bag
5-year warranty for the vessel.
The table below assists you in finding the relevant product based on its variant. For more details, please download the datasheet above.
Art. No. |
---|