Features and Benefits

5 in 1 concept reduces costs

The installation of a valve with 5 functions reduces the investment and the installation time.

Saves energy and money

Balanced and pressure independent circuits protects systems against over flows and too high energy consumption.

Zone control

Time controlled circuits can save up to 20% energy.

Noise protection

Differential pressure control protects control valves from too high differential pressure.

Applications

Heating and cooling systems.

Functions

Control

Differential pressure control

Isolation (for use during system maintenance – see "Leakage rate")

Measuring (ΔH, t, q)

Pre-setting (max. flow)

Pressure class [PN]

PN 16

Differential pressure (ΔH)

Max. differential pressure (ΔHmax):
400 kPa = 4 bar
Min. differential pressure (ΔHmin):
DN 10: 20 kPa = 0,20 bar
DN 15: 18 kPa = 0,18 bar
DN 20: 21 kPa = 0,21 bar
DN 25: 25 kPa = 0,25 bar
(Valid for the most demanding settings. Other settings will require a lower ΔH. Check with graphs under "Sizing" or software HySelect.)
ΔHmax = The maximum allowed pressure drop over the circuit, to fulfill all stated performances.
ΔHmin = The minimum needed pressure drop over the circuit, for proper differential pressure control.,

Setting range

(ΔpL 10 kPa)

DN 10: 16-71 l/h

DN 15: 60-300 l/h

DN 20: 160-840 l/h

DN 25: 280-1500 l/h

Indication of recommended setting range. For more detailed information see "Sizing".

Temperature

Max. working temperature: 120°C

Min. working temperature: -20°C

Media

Water or neutral fluids, water-glycol mixtures (0-57%).

Characteristics

Linear, best suited for on/off control

Leakage rate

Leakage flow ≤ 0.01% of max. q, max (max. setting) and correct flow direction. (Class IV according to EN 60534-4).

Lift

4 mm

Actuators

See separate technical documentation on EMO T.

Marking

TA, IMI, PN 16, DN and flow direction arrow.
Grey handwheel: TA-COMPACT-DP and DN. ,

Connection

External thread according to ISO 228.

Connection to actuator

M30x1.5

Material

Valve body: AMETAL®

Valve insert: AMETAL®

Valve plug: Brass CW724R (CuZn21Si3P)

Spindle: Stainless steel

Spindle seal: EPDM O-ring

Δp insert: AMETAL®, PPS (polyphenylsulphide)

Membrane: EPDM and HNBR

Springs: Stainless steel

O-rings: EPDM

AMETAL® is the dezincification resistant alloy of IMI Hydronic Engineering.