TA-Slider 1600 Fail-safe Plus
Digitally configurable proportional push-pull actuator with electronic fail-safe function – 1600 N
Digitally configurable fail-safe actuators for all control systems with or without change-over. Wide range of setup possibilities gives high flexibility to adapt parameters on-site. Fully programmable binary input, relay and adjustable max. stroke of the valve bring new opportunities for advanced hydronic control and balancing.
Product branding

Features and Benefits
Fully configurable fail-safe
Setting of stroke position (extended, retracted or intermediate position) and delay feature for entering/leaving fail-safe mode for a reliable and optimal fail-safe function.
Convenient, reliable setup
Fully customisable by smartphone via Bluetooth using a TA-Dongle.
Fully configurable
More than 200 setup options allow input and output signals, binary input, relay, characteristics and many other parameters to be configured.
Easy diagnostics
Tracks the last 10 errors to allow system faults to be found quickly and health check of fail-safe function.
Functions
3-point control
Delayed start-up
Diagnostic/Logging
Electronic fail-safe function
Error safe position
Manual override
Minimum stroke setting
Mode, status and position indication
On-off control
Output signal VDC
Proportional control
Stroke detection
Stroke limitation setting
Valve blockage protection
Valve clogging detection
Temperature
Media temperature: 0°C – +120°C
Operating environment: 0°C – +50°C (5-95%RH, non-condensing)
Storage environment: -20°C – +50°C (5-95%RH, non-condensing)
Control speed
3, 4, 6, 8, 12 or 16 s/mm
Default setting: 3 s/mm
Supply voltage [V]
24 VAC/VDC ±15%., 100-240 VAC ±10%., Frequency 50/60 Hz ±3 Hz
Power consumption
24 VAC/VDC:
Peak: < 21.7 VA (VAC); < 8.7 W (VDC)
Operation: < 12.0 VA (VAC); < 6.0 W (VDC)
Standby: < 1.8 VA (VAC); < 0.7 W (VDC)
100-240 VAC:
Peak: < 20.8 VA (VAC)
Operation: < 15.6 VA (VAC)
Standby: < 4.3 VA (VAC)
Peak consumption occurs for a short period after a power cut for recharging capacitors.
Input signal
0(2)-10 VDC, Ri 47 kΩ.
0.33 Hz low pass filter.
0(4)-20 mA R i 500 Ω.
Adjustable hysteresis sensitivity 0.1-0.5 VDC.
Default setting: Proportional 0-10 VDC
Proportional dual-range (for change-over): 0-3.3 / 6.7-10 VDC, 10-6.7 / 3.3-0 VDC, 2-4.7 / 7.3-10 VDC or 10-7.3 / 4.7-2 VDC.
Proportional: 0-10, 10-0, 2-10 or 10-2 VDC; 0-20, 20-0, 4-20 or 20-4 mA
Proportional split-range: 0-5, 5-0, 5-10 or 10-5 VDC; 0-4.5, 4.5-0, 5.5-10 or 10-5.5 VDC; 2-6, 6-2, 6-10 or 10-6 VDC; 0-10, 10-0, 10-20 or 20-10 mA; 4-12, 12-4, 12-20 or 20-12 mA
Output signal
0(2)-10 VDC, max. 8 mA, min. 1.25 kΩ.
Default setting: Proportional 0-10 VDC
Plus version: 0(4)-20 mA, max. 700 Ω.
Ranges: See “Input signal”.
Stroke
Automatic detection of the valve lift (stroke detection)
Max. 33 mm
Noise level
Max. 40 dBA
Marking
IMI TA, product name, article No. and technical specification.
LED indication description.
Colour
Orange RAL 2011, grey RAL 7043.
Adjusting force
1600 N
Connection to valve
By two M8 screws to the valve and by quick connection to the stem
Cable
Wire cross-section*: 0.5-2.0 mm2
Protection class I: H05VV-F or similar
Protection class III: LiYY or similar
*) Note: Wire cross-sections must be chosen according to actuator power consumption and line length, such as the voltage supply to the actuator does not go below 20.4 VAC/VDC (24 VAC/VDC minus 15%).
In case of VDC input signal on a 24 VAC/VDC powered actuator, the voltage drop on neutral line must be smaller than the defined hysteresis level for the VDC input signal.
Material
Ingress protection
IP54 all directions (according to EN 60529)
Protection class
100-240 VAC: Class I.
24 VAC/VDC: Class I
(according to EN 61140)
Certifications and directives
EMC-D. 2014/30/EU: EN 60730-1, -2-14.
LV-D. 2014/35/EU: EN 60730-1, -2-14.
RoHS-D. 2011/65/EU: EN 63000
The table below assists you in finding the relevant product based on its variant. For more details, please download the datasheet above.
Art. No. |
---|