
TA-Slider 1600 T-2T
Digitally configurable proportional push-pull actuator with temperature measurement capability – 1600 N
Digitally configurable actuators with temperature measurement capability for all control systems with or without Bus communication. To be mounted on a PIBCV for tackling ΔT syndrome or for handling change-over based on T supply or ΔT sign detection. Wide range of setup possibilities gives high flexibility to adapt parameters on-site. Fully programmable binary input, relay and adjustable max. stroke of the valve bring new opportunities for advanced hydronic control and balancing.
Product branding

Features and Benefits
Functions
3-point control
Automatic change-over function
Delayed start-up
ΔT and temperature return limitation
Diagnostic/Logging
Error safe position
Manual override
Minimum stroke setting
Mode, status and position indication
On-off control
Output signal VDC
Proportional control
Reading (supply/return temperature, ΔT, position)
Stroke detection
Stroke limitation setting
Valve blockage protection
Valve clogging detection
Temperature
Media temperature: 0°C – +120°C
Operating environment: 0°C – +50°C (5-95%RH, non-condensing)
Storage environment: -20°C – +70°C (5-95%RH, non-condensing)
Absolute temperature
PT1000 Class AA: ±0.1°C at 0°C
PT1000 Class B: ±0.3°C at 0°C
Control speed
3, 4, 6, 8, 12 or 16 s/mm
Default setting: 3 s/mm
Supply voltage [V]
24 VAC/VDC ±15%. Frequency 50/60 Hz ±3 Hz
Power consumption
Input signal
0(2)-10 VDC, Ri 47 kΩ.
0(4)-20 mA R i 500 Ω.
Adjustable sensitivity 0.1-0.5 VDC; 0.33 Hz low pass filter.
Default setting: Proportional 0-10 VDC
Proportional dual-range (for change-over): 0-3.3 / 6.7-10 VDC, 10-6.7 / 3.3-0 VDC, 2-4.7 / 7.3-10 VDC or 10-7.3 / 4.7-2 VDC.
Proportional: 0-10, 10-0, 2-10 or 10-2 VDC; 0-20, 20-0, 4-20 or 20-4 mA
Proportional split-range: 0-5, 5-0, 5-10 or 10-5 VDC; 0-4.5, 4.5-0, 5.5-10 or 10-5.5 VDC; 2-6, 6-2, 6-10 or 10-6 VDC; 0-10, 10-0, 10-20 or 20-10 mA; 4-12, 12-4, 12-20 or 20-12 mA
Output signal
0(2)-10 VDC, max. 8 mA, min. 1.25 kΩ.
Default setting: Proportional 0-10 VDC
Plus version: 0(4)-20 mA, max. 700 Ω.
Ranges: See “Input signal”.
Characteristics
Default setting: Linear.
Linear, EQM 0.25 and inverted EQM 0.25.
Measurement accuracy
Time constant τ (63%)
In valve measuring point: 5s
Surface mounted: 20s
Temperature pocket: 9s
Stroke
Automatic detection of the valve lift (stroke detection)
Max. 33 mm
Noise level
Max. 40 dBA
Marking
Colour
Orange RAL 2011, grey RAL 7043.
Adjusting force
1600 N
Connection to valve
By two M8 screws to the valve and by quick connection to the stem
Temperature sensor cable
Halogen free, fire class IEC 60332-3-24 (cat. C).
Cable
Material
Ingress protection
IP54 all directions (according to EN 60529)
Protection class
(according to EN 61140)
Class I
Weight
1,6 kg
Certifications and directives
EMC-D. 2014/30/EU: EN 60730-1, -2-14.
LV-D. 2014/35/EU: EN 60730-1, -2-14.
RoHS-D. 2011/65/EU: EN 63000
The table below assists you in finding the relevant product based on its variant. For more details, please download the datasheet above.
Art. No. |
---|