Skip to main content
TA-Slider 750

TA-Slider 750

Digitally configurable proportional push-pull actuator – 750 N

Digitally configurable actuators for all control systems with or without Bus communication. Wide range of setup possibilities gives high flexibility to adapt parameters on-site. Fully programmable binary input, relay and adjustable max. stroke of the valve bring new opportunities for advanced hydronic control and balancing.

Technical SpecificationsTA-Slider_750_EN_low.pdf

Features and Benefits

Convenient, reliable setup

Fully customisable by smartphone via Bluetooth using a TA-Dongle.

Fully configurable

More than 200 setup options allow input and output signals, binary input, relay, characteristics and many other parameters to be configured.

Easy diagnostics

Tracks the last 10 errors to allow system faults to be found quickly.

Perfection in connectivity

Communication with the most used Bus protocols.

Functions

3-point control

Delayed start-up

Diagnostic/Logging

Error safe position

Manual override

Minimum stroke setting

Mode, status and position indication

On-off control

Output signal VDC

Plus version: With optional BUS communication board. + ModBus or BACnet. With optional relay board. + 1 binary input, max. 100 Ω, cable max. 10 m or shielded. + 2 relays, max. 5A, 30 VDC/250 VAC on resistive load. + Output signal in mA

Proportional control

Stroke detection

Stroke limitation setting

Valve blockage protection

Valve clogging detection

Noise level

Max. 40 dBA

Supply voltage [V]

24 VAC/VDC ±15%., 100-240 VAC ±10%., Frequency 50/60 Hz ±3 Hz

Connection to valve

By two M8 screws to the valve and by quick connection to the stem

Ingress protection

IP54 all directions (according to EN 60529)

Temperature

Media temperature: 0°C – +120°C

Operating environment: 0°C – +50°C (5-95%RH, non-condensing)

Storage environment: -20°C – +70°C (5-95%RH, non-condensing)

Input signal

0(2)-10 VDC, Ri 47 kΩ.

0(4)-20 mA R i 500 Ω.

Adjustable sensitivity 0.1-0.5 VDC; 0.33 Hz low pass filter.

Default setting: Proportional 0-10 VDC

Proportional dual-range (for change-over): 0-3.3 / 6.7-10 VDC, 10-6.7 / 3.3-0 VDC, 2-4.7 / 7.3-10 VDC or 10-7.3 / 4.7-2 VDC.

Proportional: 0-10, 10-0, 2-10 or 10-2 VDC; 0-20, 20-0, 4-20 or 20-4 mA

Proportional split-range: 0-5, 5-0, 5-10 or 10-5 VDC; 0-4.5, 4.5-0, 5.5-10 or 10-5.5 VDC; 2-6, 6-2, 6-10 or 10-6 VDC; 0-10, 10-0, 10-20 or 20-10 mA; 4-12, 12-4, 12-20 or 20-12 mA

Control speed

3, 4, 6, 8, 12 or 16 s/mm

Default setting: 3 s/mm

Output signal

0(2)-10 VDC, max. 8 mA, min. 1.25 kΩ.

Default setting: Proportional 0-10 VDC

Plus version: 0(4)-20 mA, max. 700 Ω.

Ranges: See “Input signal”.

Adjusting force

750 N

Protection class

100-240 VAC: Class I.

24 VAC/VDC: Plus version with optional relay board, Class I.

(according to EN 61140)

All other versions, Class III safety extra low voltage.

Stroke

22 mm

Automatic detection of the valve lift (stroke detection)

Certifications and directives

EMC-D. 2014/30/EU: EN 60730-1, -2-14.

LV-D. 2014/35/EU: EN 60730-1, -2-14.

RoHS-D. 2011/65/EU: EN 63000

Cable

Cable: Wire cross-section*: 0.5-2.0 mm2
Protection class I: H05VV-F or similar
Protection class III: LiYY or similar

*) Note: Wire cross-sections must be chosen according to actuator power consumption and line length, such as the voltage supply to the actuator does not go below 20.4 VAC/VDC (24 VAC/VDC minus 15%).
In case of VDC input signal on a 24 VAC/VDC powered actuator, the voltage drop on neutral line must be smaller than the defined hysteresis level for the VDC input signal

Colour

Orange RAL 2011, grey RAL 7043.

Marking

IMI TA, product name, article No. and technical specification.

LED indication description.

Material

Cover: PBT

Bracket: Alu EN44200

Power consumption

Power consumption: 24 VAC/VDC:
Operation: 8 VA (VAC); 4.5 W (VDC)
Standby: 1 VA (VAC); 0.5 W (VDC)
100-240 VAC:
Operation: 9.7 VA (VAC)
Standby: 1.8 VA (VAC),