TA-COMFORT radiant heating interface unit with Dynacon Eclipse

TA-COMFORT radiant heating interface unit with Dynacon Eclipse

Heating interface unit for radiant heating with automatic flow control

Factory prefabricated underfloor heating station including Dynacon Eclipse manifold with automatic flow controllers per heating circuit. With distributor strip for up to 8 zones (rooms). Dynacon Eclipse adjusts the flow rate in the individual heating circuits directly in l/h. This means hydraulic balancing is achieved in one simple operation. The set flow rate is constantly adapted, i.e. if the rate becomes too high, e.g. due to closing adjacent circuits, Dynacon Eclipse controls the flow automatically to the set value. The control cartridge always ensures a constant flow. This makes Dynacon Eclipse heating circuit manifolds a time and cost-saving solution especially for system commissioning.

Technical SpecificationsTA-COMFORT_radiant_heating_unit_EN_low.pdf
Technical SpecificationsTA-COMFORT_radiant_heating_unit_ES_low.pdf

Product branding

imi_ta

Features and Benefits

Complete systems for decentralised heat distribution

Provides the dwelling with heat, controlling the heat requirements.

Automatic hydraulic balancing

Due to integrated flow controller inside each thermostatic insert

Flow indicator for each heating circuit

For functional check

Actuator EMOtec First-Open

Normally closed version with First-Open function. Simple functional testing by means of position indicator.

With distributor strip

For up to 8 zones (rooms)

Applications

Floor heating systems

Functions

Draining

Filling

Flow limitation

Measuring (ball valves with connection for direct measurement in supply and return)

Shut-off

Flushing

Individual room temperature control with actuator or thermostatic head with remote dial<

Venting

Pressure class [PN]

PN 6

Differential pressure (ΔpV)

Max. differential pressure:
60 kPa (<30 dB(A))
Min. differential pressure:
30 – 150 l/h = 17 kPa
150 – 300 l/h = 25 kPa

Flow range

The flow can be stepless pre-set within the range: 30-300 l/h.
Delivery setting: Commissioning setting.
Max. 2,5 m3/h per heating circuit manifold.

Temperature

Max. working temperature: 70°C

Min. working temperature: -5°C

Marking

IMI Heimeier

Material

Manifold: Stainless steel 1.4301
Connection fittings: Nickel-plated brass.

Thermostatic insert: Brass
O-rings: EPDM
Valve disc: EPDM
Spring: stainless steel
Thermostatic insert: Brass, PPS (polyphenylsulphide) and SPS (syndiotactic polystyrene)
Spindle: Niro-steel spindle with double O-ring seal.

Flow meter: Heat-resistant plastic and stainless steel. Brass. EPDM seals.

Filling, draining, flushing and venting device: Nickel-plated brass and plastic. EPDM seals.

Ball valves: Brass, PTFE and EPDM seals.
Heat meter piece: Steel
Couplings: Brass

Distribution cabinet: Sheet steel galvanized. Frame and door powder-coated, white RAL 9016.