Skip to main content
TA-Slider 500 T-2T

TA-Slider 500 T-2T

Digitally configurable proportional push-pull actuator with temperature measurement capability – 500/300 N

Digitally configurable actuators with temperature measurement capability and operation, to be used as a terminal unit actuator mounted on a PIBCV for tackling ΔT syndrome or for handling changeover based on T supply or ΔT sign detection. A wide range of setup options provide extensive flexibility for on-site parameter adaptation. Fully programmable binary input, relay and adjustable max. stroke of the valve bring new opportunities for advanced hydronic control and balancing.

Technical SpecificationsTA-Slider_500_T-2T_EN_low.pdf

Product branding

imi_ta

Features and Benefits

Optional ΔT and temperature return limitation

Optimize the efficiency of your production units by ensuring optimal temperature regimes.

Convenient, reliable setup

Fully customisable by smartphone via Bluetooth using a TA-Dongle.

Change-over functionality

Switch between heating/cooling flows according to input signal or automatically using T supply or ΔT sign detection.

Easy diagnostics

Tracks the last 10 errors to allow system faults to be found quickly.

Quick copying of settings

Setup configuration can be copied quickly from the TA-Dongle to identical TA-Slider actuators.

Functions

Automatic change-over function

Delayed start-up

ΔT and temperature return limitation

Diagnostic/Logging

Error safe position

Manual override (TA-Dongle)

Minimum stroke setting

Mode, status and position indication

Proportional control

Reading (supply/return temperature, ΔT, position)

Stroke detection

Stroke limitation setting

Valve blockage protection

Valve clogging detection

Temperature

Max. medium temperature: 120°C

Operating environment: 0°C – +50°C (5-95%RH, non-condensing)

Storage environment: -20°C – +70°C (5-95%RH, non-condensing)

Absolute temperature

PT1000 Class AA: ±0.1°C at 0°C

PT1000 Class B: ±0.3°C at 0°C

Control speed

4 or 6 s/mm.

Default setting: 4 s/mm.

Supply voltage [V]

24 VAC/VDC ±15%. Frequency 50/60 Hz ±3 Hz

Power consumption

Operation: < 3.6 VA (VAC); < 1.7 W (VDC)

Standby: < 1.3 VA (VAC); < 0.6 W (VDC)


Input signal

0(2)-10 VDC, Ri 47 kΩ.

0.33 Hz low pass filter.

Adjustable hysteresis sensitivity 0.1-0.5 VDC.

Default setting: Proportional 0-10 VDC

Proportional: 0-10, 10-0, 2-10 or 10-2 VDC.

Proportional dual-range (for change-over): 0-3.3 / 6.7-10 VDC, 2-4.7 / 7.3-10 VDC, 0-4.5 / 5.5-10 VDC or 2-5.5 / 6.5-10 VDC.

Proportional split-range: 0-5, 5-0, 5-10 or 10-5 VDC; 0-4.5, 4.5-0, 5.5-10 or 10-5.5 VDC; 2-6, 6-2, 6-10 or 10-6 VDC.

Output signal

0(2)-10 VDC, max. 8 mA, min. 1.25 kΩ.

Default setting: Proportional 0-10 VDC

Ranges: See “Input signal”.

Characteristics

Default setting: Linear.

Linear, EQM 0.25 and inverted EQM 0.25.

Measurement accuracy

Temperature pocket: Class AA
In valve measuring point: Class B
Surface mounted: Class B

T version

1 binary input, max. 100 Ω, cable max. 10 m or shielded.

1 pre-mounted PT1000 to be inserted in valve measuring point.

Output signal

2T version

1 binary input, max. 100 Ω, cable max. 10 m or shielded.

Output signal

1 pre-mounted cable with possibility to connect 2 PT1000 (see section “Sensors”)

Time constant τ (63%)

In valve measuring point: 5s

Surface mounted: 20s

Temperature pocket: 9s

Stroke

16,2 mm

Standard

EN 60730

Noise level

Max. 30 dBA

Marking

Label: IMI TA, CE, product name, article No. and technical specification.

Colour

White RAL 9016, grey RAL 7047.

Adjusting force

Pull 300 N

Push 500 N

Connection to valve

Swivelling nut M30x1,5

Temperature sensor cable

2T version: Length, see section “Sensors”.

Halogen free, fire class IEC 60332-3-24 (cat. C).

T version: Length 160 mm.

Cable

3.28 ft, 6.56 ft or 16.4 ft. Halogen free with wire end sleeves. Fire class B2ca – s1a, d1, a1 according to EN 50575. Type LiYY, 5x23 AWG (5x0.25 mm2 ).

Material

Cover: PC/ABS GF8
Housing: PA GF40.
Swivelling nut: Nickel-plated brass.

Ingress protection

IP54 all directions (according to EN 60529)

Protection class

III (SELV)

(according to EN 61140)

Weight

TA-Slider 500 2T: 0.34 kg, 1 m cable; 0.39 kg, 2 m cable; 0.54 kg, 5 m cable

TA-Slider 500 T: 0.29 kg, 1 m cable; 0.34 kg, 2 m cable; 0.49 kg, 5 m cable

Certifications and directives

EMC-D. 2014/30/EU: EN 60730-1, -2-14.

LV-D. 2014/35/EU: EN 60730-1, -2-14.

RoHS-D. 2011/65/EU: EN 63000

The table below assists you in finding the relevant product based on its variant. For more details, please download the datasheet above.