Skip to main content
Transfero TV Connect

Transfero TV Connect

For heating systems up to 8 MW and cooling systems up to 13 MW$

Transfero TV Connect is a precision pressure maintenance device for heating and solar systems up to 8 MW, and chilled water systems up to 13 MW. Its use is particularly recommended where high performance, compact design and precision are required. The new BrainCube Connect control panel allows a new level of connectivity, enabling communication with the BMS system, other BrainCubes as well as remote operation of the pressurisation system through live viewing.
Technical SpecificationsPlanning_and_Calculation_EN_low.pdf
Technical SpecificationsTransfero_TV_Connect_EN_low.pdf

Features and Benefits

2 in 1

The only pressurisation unit with integrated cyclonic vacuum degassing

Higher Efficiency Cyclonic vacuum degassing

At least 50% higher efficiency than most other vacuum degassing systems.

Easy Commissioning, Remote Access and Trouble-shooting

Automatic calibration and integrated standard connections to our IMI Webserver and to BMS.

Applications

Heating, solar and cooling water systems.

For systems according to EN 12828, SWKI HE301-01, solar systems according to EN 12976, ENV 12977, with on-site excess temperature protection in case of power outage.

Heating, solar and chilled water systems.

Accuracy

Precision pressure maintenance ±0,2 bar

Supply voltage [V]

1 x 230 V (± 10 %) / 50 Hz

Media

Ethylene or propylene glycol-based antifreeze up to 50%.

Non-aggressive and non-toxic system media.

Pressure

Max. admissible pressure, PS: see Articles

Min. admissible pressure, PSmin: -1 bar

Standard

Constructed according to LV-D. 2014/35/EU, EMC-D. 2014/30/EU

Temperature

Max. admissible temperature, TS: 90°C

Min. admissible temperature, TSmin: 0 °C

Max. admissible ambient temperature, TA: 40°C

Min. admissible bag temperature, TBmin: 5°C

Enclosure class

IP54 according to EN 60529

For PED purposes

Min. admissible temperature, TSmin: -10°C

Max. admissible temperature, TS: 120°C

Mechanical connections

Sin1/Sin2: inlet from the system G3/4"

Sout: outlet to the system G3/4"

Sv: connection of the vessel G1 1/4"

Swm: inlet water make-up G3/4"

Material

Metal components with medium contact: carbon steel, cast iron, stainless steel, AMETAL®, brass, gunmetal.

Electrical connection

Onsite fuses according to power demand and local norms
4 potential free outputs (NO) for external alarm indication (230V max. 2A)
1 RS 485 In/Output
1 Ethernet RJ45 plug socket
1 USB Hub plug socket
Terminal strip in PowerCube for direct wiring

Expansion vessel

Only together with TecBox Control Unit. See Applications under Technical description - TecBox Control Unit.