Skip to main content
Simply Vento

Simply Vento

For heating systems

Simply Vento is a cyclonic vacuum degasser for heating systems. Through the process of rotating the water in a special cyclonic vacuum vessel, the gases are separated completely from the water. Its use is particularly recommended where performance, compact design and precision are required. The BrainCube Connect control panel allows a new level of connectivity, enabling communication with the BMS system, other BrainCubes as well as remote operation of the pressurisation system through live viewing.

Technical SpecificationsAccessories_EN_low.pdf
Technical SpecificationsSimply_Vento_PL_low.pdf
Technical SpecificationsPlanning_and_Calculation_EN_low.pdf
Technical SpecificationsSimply_Vento_EN_low.pdf

Product branding

imi_pneumatex

Features and Benefits

Higher Efficiency Cyclonic vacuum degassing

Significantly higher efficiency than most other vacuum degassing systems.

Compact design for floor and wall hanging installation

Easy Commissioning, Remote Access and Trouble-shooting

Integrated standard connections to our IMI Webserver and to BMS.

Optional sound absorbing wall bracket

For Vento Compact in installations particularly sensitive to structure-borne sound.

Plug & Play installation and start-up

Connect unit to the installation
Plug in power supply
Follow the instructions displayed on the BrainCube

– Control unit TecBox

Applications

For systems according to EN 12828, SWKI HE301-01, EN 12976, ENV 12977, EN 12952, EN 12953

Heating systems.

Pressure

Max. admissible pressure, PS: 10 bar

Min. admissible pressure, PSmin: -1 bar

Temperature

Max. admissible temperature, TS: 90°C

Min. admissible temperature, TSmin: 0 °C

Max. admissible ambient temperature, TA: 40°C

Min. admissible ambient temperature, TAmin: 0°C

Media

Ethylene or propylene glycol-based antifreeze up to 50%.

Non-aggressive and non-toxic system media.

Supply voltage [V]

1 x 230 V (± 10 %) / 50 Hz

Transportation and storage

In frostless, dry places

Standard

Constructed according to LV-D. 2014/35/EU, EMC-D. 2014/30/EU

Mechanical connections

Sin1: inlet from the system G1/2"

Sout: outlet to the system G1/2"

Electrical connection

Onsite fuses according to power demand and local norms

3 potential-free outputs (NO) for external alarm indication (230V max. 2A)

1 RS 485 In/Output

1 Ethernet RJ45 plug socket

1 USB Hub plug socket

Material

Metal components with medium contact: carbon steel, cast iron, stainless steel, AMETAL®, brass, gunmetal.

Enclosure class

IP54 according to EN 60529