TA-Nano
Pressure independent balancing and control valve (PIBCV)
The pressure-independent balancing and control valve TA-Nano ensures optimum performance over a long life. Adjustable maximum flow enables design flow and eliminates overflows for accurate hydronic control. The TA-Nano Plus together with our balancing instruments enables advanced measuring and diagnostics.
Product branding

Features and Benefits
Smallest PIBCV in the market fitting within the most constrained area
Slim and compact shape simplifies installation.
Precise hydronic balancing
Smoothly adjustable setting of max. flow prevents over flow through terminal unit.
Full control of the system (Plus)
Exact flow measuring and unique diagnostic functions for ultimate energy savings and highly reliable system.
Precise setting and ease of commissioning
Valve position visible when actuator is mounted, easy valve identification with colour coding.
High reliability
High resistance to corrosion using AMETAL®, strong resistance to dirt and completely tight valve.
Applications
Heating and cooling systems.
Functions
Control
Differential pressure control
Isolation (for use during system maintenance – see "Leakage rate")
Pre-setting (max. flow)
Dimension [DN]
DN 10-25
Pressure class [PN]
PN 25
Differential pressure (ΔpV)
Max. differential pressure (ΔpVmax): 600 kPa = 6 bar
Min. differential pressure (ΔpVmin):
DN 10 NF/15 LF/15 NF: 15 kPa = 0.15 bar
DN 15 HF: 20 kPa = 0.20 bar
DN 20 NF: 18 kPa = 0.18 bar
DN 20 HF: 30 kPa = 0.30 bar
DN 25 NF: 25 kPa = 0.25 bar
(Valid for position 10, fully open. Other
positions will require lower differential
pressure, check with the software
HySelect.)
ΔpVmax = The maximum allowed
pressure drop over the valve to fulfill all
stated performances.
ΔpVmin = The minimum recommended
pressure drop over the valve, for proper
differential pressure control.
Flow range
The flow (qmax) can be set within the range:
DN 10 NF: 18 - 180 l/h
DN 15 LF: 28 - 280 l/h
DN 15 NF: 54 - 540 l/h
DN 15 HF: 95 - 950 l/h
DN 20 NF: 120 - 1200 l/h
DN 20 HF: 160 - 1600 l/h
DN 25 NF: 220 - 2200 l/h
qmax = l/h at each setting and fully open valve plug.
LF = Low flow
NF = Normal flow
HF = High flow
Temperature
Max. working temperature: 120°C
Min. working temperature: -10°C
Media
Water or neutral fluids, water-glycol mixtures (0-57%).
Characteristics
Linear, best suited for on/off control
Leakage rate
(Class VI according to EN 60534-4).
Tight sealing
Lift
4 mm
Actuators
See separate technical documentation on EMO T, EMO TM, TA-TRI and TA-Slider 160.
Marking
IMI, PN 25, DN and flow direction arrow.
Insert: TA-Nano, DN (+LF/NF/HF)
LF: Red insert.
NF: White insert.
HF: Grey insert.
Connection
External thread according to ISO 228.
Internal thread according to ISO 7
Connection to actuator
M30x1.5
Material
Valve body: AMETAL®
Valve insert: AMETAL® and PPS
Valve plug: PPS
Spindle: Stainless steel
Spindle seal: EPDM
O-ring Δp insert: Brass CW614
Membrane: EPDM
Springs: Stainless steel
O-rings: EPDM
Setting wheel: PA
Measuring points: AMETAL®
Sealings: EPDM
Caps: Polyamide and TPE
AMETAL® is the dezincification resistant alloy of IMI.
The table below assists you in finding the relevant product based on its variant. For more details, please download the datasheet above.
Art. No. |
---|