TA-Slider 160
Digitally configurable proportional push actuator – 160/200 N
Digitally configurable actuators with or without change-over, and a wide range of setup options provide extensive flexibility for on-site parameter adaptation. Fully programmable binary input, relay and adjustable max. stroke of the valve bring new opportunities for advanced hydronic control and balancing.
Features and Benefits
Convenient, reliable setup
Fully customisable by smartphone via Bluetooth using a TA-Dongle.
Fully configurable
More than 200 setup options allow input and output signals, binary input, relay, characteristics and many other parameters to be configured.
Easy diagnostics
Tracks the last 10 errors to allow system faults to be found quickly.
Quick copying of settings
Setup configuration can be copied quickly from the TA-Dongle to identical TA-Slider actuators.
Noise level
Max. 30 dBA
Supply voltage [V]
24 VAC/VDC ±15%., Frequency 50/60 Hz ±3 Hz., CO version: , 24 VAC ±15%., Frequency 50/60 Hz ±3 Hz
Connection to valve
Swivelling nut M30x1,5
Ingress protection
IP54 all directions (according to EN 60529)
Temperature
Operating environment: 0°C – +50°C (5-95%RH, non-condensing)
Storage environment: -20°C – +70°C (5-95%RH, non-condensing)
Input signal
0(2)-10 VDC, Ri 47 kΩ.
Adjustable hysteresis sensitivity 0.1-0.5 VDC; 0.33 Hz low pass filter.
Default setting: Proportional 0-10 VDC
Proportional: 0-10, 10-0, 2-10 or 10-2 VDC.
Proportional dual-range (for change-over): 0-3.3 / 6.7-10 VDC, 2-4.7 / 7.3-10 VDC, 0-4.5 / 5.5-10 VDC or 2-5.5 / 6.5-10 VDC.
Proportional split-range: 0-5, 5-0, 5-10 or 10-5 VDC; 0-4.5, 4.5-0, 5.5-10 or 10-5.5 VDC; 2-6, 6-2, 6-10 or 10-6 VDC.
Control speed
10 s/mm
Output signal
I/O, Plus, CO versions: 0(2)-10 VDC, max. 8 mA, min. 1.25 kΩ.
Default setting: Proportional 0-10 VDC
Ranges: See “Input signal”.
Adjusting force
160/200 N
Self-adjusting for IMI Hydronic Engineering valves.
Protection class
(according to EN 61140)
III (SELV) TA-Slider 160, 160 I/O, 160 CO
II TA-Slider 160 Plus (protective insulation)
Stroke
6,9 mm
Automatic detection of the valve lift (stroke detection)
Certifications and directives
EMC-D. 2014/30/EU: EN 60730-1, -2-14.
LV-D. 2014/35/EU: EN 60730-1, -2-14.
RoHS-D. 2011/65/EU: EN 63000
Cable
Halogen free as option, fire class B2ca – s1a, d1, a1 according to EN 50575.
TA-Slider 160: type LiYY, 3x0.25 mm2.
TA-Slider 160 I/O: type LiYY, 5x0.25 mm2.
TA-Slider 160 Plus: type LiYY, 5x0.25 mm2 and relay cable type H03VV-F, 3x0.75 mm2, with wire end sleeves.
TA-Slider 160 CO: type LiYY, 5x0.25 mm2 and relay cable type LiYY, 3x0.34 mm2, with connector to actuator TA-M106.
Colour
White RAL 9016, grey RAL 7047.,
Marking
Label: IMI TA, CE, product name, article No. and technical specification.,
Power consumption
Standby: 0.5 VA (VAC); 0.25 W (VDC)
I/OCO versions:
Operation: 1.3 VA (VAC); 0.7 W (VDC)
Standby: 0.5 VA (VAC); 0.25 W (VDC)
Plus version:
Operation: 1.8 VA (VAC); 1.0 W (VDC)
Standby: 0.5 VA (VAC); 0.25 W (VDC)
CO version: TA-M106 actuator consumption must be added separately