With external compressed air supply, for heating systems up to 4 MW and cooling systems up to 6 MW
The Compresso CX Connect is a precision pressurisation system with external supply of compressed air for heating, solar and chilled water systems. It is especially suitable in situations where compactness and accuracy are required. In terms of pressurisation capacity, the system lies between the Statico and Transfero ranges. The new BrainCube Connect control panel offers a new level of connectivity, enabling communication with the BMS system, other BrainCubes as well as remote operation of the pressurisation system through live viewing.
Product branding

Features and Benefits
Improved design for easier and more comfortable operation
Resistant 3.5" TFT illuminated colour touch display. Intuitive and user friendly menu. Web based interface with remote control and live view. BrainCube Connect control panel integrated into TecBox.
Remote Access and Trouble-shooting
Remote access and commissioning support, reducing the need for high skilled staff to perform operations. Quicker response time, reduced repair costs. Data logging for system performance checks.
State-of-the-Art Connectivity
Standardised connections to BMS and remote devices available (RS485, Ethernet, USB) enabling time savings during set-up and service and unit controllability. Communication with up to 12 BrainCubes in a Master/Slave network.
Fillsafe water make-up monitoring
With the possibility to control water make-up through a Pleno P.
Applications
For systems according to EN 12828, SWKI HE301-01, solar systems according to EN 12976, ENV 12977, with on-site excess temperature protection in case of power outage.
Heating, solar and chilled water systems.
Pressure
Max. admissible pressure, PS: see Articles
Min. admissible pressure, PSmin: 0 bar
Temperature
Max. admissible ambient temperature, TA: 40°C
Min. admissible ambient temperature, TAmin: 5°C
Supply voltage [V]
1 x 230V (-6% + 10%) / 50/60 Hz
Electric load
See Articles
Accuracy
Precision pressure maintenance ±0,1 bar
Expansion vessel
Only together with Control unit TecBox. See Applications under Technical description - Control unit TecBox.
For PED purposes
Min. admissible temperature, TSmin: -10°C
Max. admissible temperature, TS: 120°C
Transportation and storage
In frostless, dry places
Standard
Constructed according to MD 2006/42/EC, Annex II 1.A EMC-D. 2014/30/EU
Material
Main materials include steel, brass, and bronze.
Enclosure class
IP 54
IP according to EN 60529