STAP – ANSI flanges
Differential pressure controller DN 65-100, adjustable set-point and shut-off function
The flanged STAP is a high-performing differential pressure controller that keeps the differential pressure over the load constant. This delivers accurate and stable modulating control, ensures less risk of noise from control valves, and results in easy balancing and commissioning. STAP’s unrivalled accuracy and compact size make it particularly suitable for use on the secondary side of heating and cooling systems.
Product branding

Features and Benefits
Adjustable set-point
Delivers desired differential pressure ensuring accurate balancing.
Shut-off function
Shut-off function makes maintenance easy and straightforward.
Measuring points
Simplifies the balancing procedure, and increases its accuracy.
Applications
Heating (not steam) and cooling systems.
Functions
Adjustable Δp
Differential pressure control
Measuring point
Shut-off
Differential pressure (ΔpV)
Setting range
20* - 80 kPa resp 40* - 160 kPa.
*) Delivery settings
(6.69-26.8 Ft H2O / 2.90-11.6 PSI resp 13.4-53.5 Ft H2O / 5.80-23.2 PSI)
Temperature
Max. working temperature: 120°C
Min. working temperature: -10°C
Media
Water or neutral fluids, water-glycol mixtures (0-57%).
Marking
Bonnet and handwheel: Label with STAP, DN, PN, ΔpL in ft H2O, psi and kPa, and bar code. ,
Connection
Flanges: Class 150 according to ASME/ANSI B16.42 (~ PN 20 according to ISO 7005-2).
Flanges
Class 150 according to ASME/ANSI B16.42 (~ PN 20 according to ISO 7005-2).
Material
Valve body: Ductile iron EN-GJS-400-15 (~ASTM A536 Grade 60-40-18, ISO 1083 Grade 400-15)
Bonnet: AMETAL®
Cone: PTFE coated AMETAL®
Spindles: AMETAL®
O-rings: EDPM rubber
Seat seal: Plug with EPDM O-ring
Membrane: Reinforced EPDM rubber
Spring: Stainless steel
Handwheel: Polyamide
AMETAL® is the dezincification resistant alloy of IMI Hydronic Engineering.
Surface treatment
Valve body: Epoxy painting.