TA-Slider 160 T-2T
Digitally configurable proportional push actuator with temperature measurement capability – 160/200 N
Digitally configurable actuators with temperature measurement capability and operation, to be used as a terminal unit actuator mounted on a PIBCV for tackling ΔT syndrome or for handling changeover based on T supply or ΔT sign detection. A wide range of setup options provide extensive flexibility for on-site parameter adaptation. Fully programmable binary input, relay and adjustable max. stroke of the valve bring new opportunities for advanced hydronic control and balancing.
Features and Benefits
Optional ΔT and temperature return limitation
Optimize the efficiency of your production units by ensuring optimal temperature regimes.Convenient, reliable setup
Fully customisable by smartphone via Bluetooth using a TA-Dongle.Change-over functionality
Switch between heating/cooling flows according to input signal or automatically using T supply or ΔT sign detection.Easy diagnostics
Tracks the last 10 errors to allow system faults to be found quickly.Quick copying of settings
Setup configuration can be copied quickly from the TA-Dongle to identical TA-Slider actuators.Functions
Automatic change-over function
Delayed start-up
ΔT and temperature return limitation
Diagnostic/Logging
Error safe position
Manual override (TA-Dongle)
Minimum stroke setting
Mode, status and position indication
Proportional control
Reading (supply/return temperature, ΔT, position)
Self-adjusting force
Stroke detection
Stroke limitation setting
Valve blockage protection
Valve clogging detection
Noise level
Max. 30 dBA
Supply voltage [V]
24 VAC/VDC ±15%. Frequency 50/60 Hz ±3 Hz
Connection to valve
Swivelling nut M30x1,5
Ingress protection
IP54 all directions (according to EN 60529)
Standard
EN 60730
T version
1 binary input, max. 100 Ω, cable max. 10 m or shielded.
1 pre-mounted PT1000 to be inserted in valve measuring point.
Output signal
Weight
TA-Slider 160 2T: 0.29 kg, 1 m cable; 0.34 kg, 2 m cable; 0.49 kg, 5 m cable
TA-Slider 160 T: 0.24 kg, 1 m cable; 0.29 kg, 2 m cable; 0.44 kg, 5 m cable
2T version
1 binary input, max. 100 Ω, cable max. 10 m or shielded.
Output signal
1 pre-mounted cable with possibility to connect 2 PT1000 (see section “Sensors”)
Temperature
Max. medium temperature: 120°C
Operating environment: 0°C – +50°C (5-95%RH, non-condensing)
Storage environment: -20°C – +70°C (5-95%RH, non-condensing)
Input signal
0(2)-10 VDC, Ri 47 kΩ.
0.33 Hz low pass filter.
Adjustable hysteresis sensitivity 0.1-0.5 VDC.
Default setting: Proportional 0-10 VDC
Proportional: 0-10, 10-0, 2-10 or 10-2 VDC.
Proportional dual-range (for change-over): 0-3.3 / 6.7-10 VDC, 2-4.7 / 7.3-10 VDC, 0-4.5 / 5.5-10 VDC or 2-5.5 / 6.5-10 VDC.
Proportional split-range: 0-5, 5-0, 5-10 or 10-5 VDC; 0-4.5, 4.5-0, 5.5-10 or 10-5.5 VDC; 2-6, 6-2, 6-10 or 10-6 VDC.
Control speed
10 s/mm
Output signal
0(2)-10 VDC, max. 8 mA, min. 1.25 kΩ.
Default setting: Proportional 0-10 VDC
Ranges: See “Input signal”.
Time constant τ (63%)
In valve measuring point: 5s
Surface mounted: 20s
Temperature pocket: 9s
Adjusting force
160/200 N
Self-adjusting for IMI Hydronic Engineering valves.
Characteristics
Default setting: Linear.
Linear, EQM 0.25 and inverted EQM 0.25.
Protection class
III (SELV)
(according to EN 61140)
Stroke
6,9 mm
Automatic detection of the valve lift (stroke detection)
Absolute temperature
PT1000 Class AA: ±0.1°C at 0°C
PT1000 Class B: ±0.3°C at 0°C
Temperature sensor cable
2T version: Length, see section “Sensors”.
Halogen free, fire class IEC 60332-3-24 (cat. C).
T version: Length 160 mm.
Certifications and directives
EMC-D. 2014/30/EU: EN 60730-1, -2-14.
LV-D. 2014/35/EU: EN 60730-1, -2-14.
RoHS-D. 2011/65/EU: EN 63000
Cable
Colour
White RAL 9016, grey RAL 7047
Marking
Label: IMI TA, CE, product name, article No. and technical specification.
Material
Power consumption
Measurement accuracy
Art. No. |
---|