Skip to main content
Thermostatic head K

Thermostatic head K

With built-in sensor and remote sensor

The thermostatic heads K are used to control the temperature of individual rooms using, for example, heaters, convectors, and radiators. The thermostatic head K range not only provides high-precision control it also is designed for exceptional ease of use. The models with remote sensor enables the installation of the thermostatic head covered by curtains, radiator facings, or other obstructions, or mounted vertically or in tight niches.

Technical SpecificationsThermostatic_head_K_EN_lq.pdf
Technical SpecificationsThermostatic_heads_General_EN_low.pdf

Product branding

imi_heimeier

Features and Benefits

Liquid-filled thermostat with high pressure power and precision control

With 2 clips for marking, limiting or blocking

Symbols for basic setting and nighttime set back

Brief data including the most important settings

Rotation direction indicator

Markings designed for the visually impaired

Applications

Heating systems.

Functions

Temperature control

Frost protection.

Markings indicate upper and lower temperature range; two energy saving clips can be used to limit settings.

Temperature range is limited on both ends and can be blocked using covered stop clips.

Differential pressure influence

With built-in sensor: 0.2 K, With remote sensor: 0.3 K

Temperature

Max. sensor temperature: 50°C (122°F)

Nominal temperature range

See each product

Water temperature influence

With built-in sensor: 0.3 K, With remote sensor: 0.3 K

Control behavior

Control behavior: Proportional controller without auxilliary energy. Liquid-filled thermostat. High pressure power, lowest hysteresis, optimal closing time. Stable control behavior even in the case of small calculated p-band variation (<1K).

Control accuracy, CA value

0.2 K

Hysteresis

With built-in sensor: 0.15 K

With remote sensor: 0.2 K

Closing time

With built-in sensor 19 min, With remote sensor: Horizontally fitted sensor 12 min, Vertically fitted sensor 15 min

Marking

Heimeier and KEYMARK symbol.
Setting numbers.
Symbols for basic setting and nighttime reduction.
Brief data including the most important settings.
Setting indicators on the face of the head and markings designed for the visually impaired.
Rotation direction indicator.

Colour

White RAL 9016

Connection

Designed to be mounted on all IMI Heimeier thermostatic valve bodies and radiators with integrated valves which have an M30x1.5 thermostatic insert.

Material

ABS, PA6.6GF30, brass, steel,
Liquid-filled thermostat.

The table below assists you in finding the relevant product based on its variant. For more details, please download the datasheet above.