Skip to main content
Transfero TVI Connect

Transfero TVI Connect

For higher pressures in heating systems up to 8 MW and cooling systems up to 13 MW

The Transfero TVI Connect is a precision pressure maintenance device for higher pressures in heating and solar systems up to 8 MW, and chilled water systems up to 13 MW. Its use is particularly recommended where high performance, compact design and precision are required. The new BrainCube Connect control panel allows a new level of connectivity, enabling communication with the BMS system and other BrainCubes, as well as remote operation of the pressurisation system through live viewing.
Technical SpecificationsPlanning_and_Calculation_EN_low.pdf
Technical SpecificationsTransfero_TVI_Connect_EN_low.pdf

Product branding

imi_pneumatex

Features and Benefits

2 in 1
The only pressurisation unit with integrated cyclonic vacuum degassing

Higher Efficiency Cyclonic vacuum degassing
At least 50% higher efficiency than most other vacuum degassing systems.

Easy Commissioning, Remote Access and Trouble-shooting
Automatic calibration and integrated standard connections to our IMI Webserver and to BMS.

Applications

Heating, solar and cooling water systems.

For systems according to EN 12828, SWKI HE301-01, solar systems according to EN 12976, ENV 12977, with on-site excess temperature protection in case of power outage.

Heating, solar and chilled water systems.

Pressure

Max. admissible pressure, PS: 25 bar

Min. admissible pressure, PSmin: -1 bar

Temperature

Max. admissible temperature, TS: 90°C

Min. admissible temperature, TSmin: 0 °C

Max. admissible ambient temperature, TA: 40°C

Min. admissible ambient temperature, TAmin: 5°C

Media

Ethylene or propylene glycol-based antifreeze up to 50%.

Non-aggressive and non-toxic system media.

Supply voltage [V]

Main voltage: 3x400V (± 10%) / 50Hz (3P+PE) Control voltage: 230V (± 10%) / 50Hz (P+N+PE)

Accuracy

accuracy_02_bar

Expansion vessel

Only together with TecBox Control Unit. See Applications under Technical description - TecBox Control Unit.

For PED purposes

Min. admissible temperature, TSmin: -10°C

Max. admissible temperature, TS: 120°C

Standard

Constructed according to MD 2006/42/EC, Annex II 1.A EMC-D. 2014/30/EU

Mechanical connections

Sin1/Sin2: inlet from the system G3/4"

Sout: outlet to the system G3/4"

Sv: connection of the vessel G1 1/4"

Swm: inlet water make-up G3/4"

Electrical connection

Onsite fuses according to power demand and local norms
4 potential free outputs (NO) for external alarm indication (230V max. 2A)
1 RS 485 In/Output
1 Ethernet RJ45 plug socket
1 USB Hub plug socket
Terminal strip in PowerCube for direct wiring

Enclosure class

IP54 according to EN 60529

The table below assists you in finding the relevant product based on its variant. For more details, please download the datasheet above.