Digitally configurable proportional push-pull actuator – 168 lbf (750 N)

Digitally configurable actuators for all control systems with or without BUS communication. Wide range of setup possibilities gives high flexibility to adapt parameters on-site. Fully programmable binary input, relay and adjustable maximum stroke of the valve bring new opportunities for advanced hydronic control and balancing.

Technical SpecificationsTA-Slider_750_EN_low.pdf

Product branding

imi_ta

Features and Benefits

Convenient, reliable setup

Fully customisable by smartphone via Bluetooth using a TA-Dongle.

Fully configurable

More than 200 setup options allow input and output signals, binary input, relay, characteristics and many other parameters to be configured.

Easy diagnostics

Tracks the last 10 errors to allow system faults to be found quickly.

Perfection in connectivity

Communication with the most used Bus protocols.

Functions

3-point control

Delayed start-up

Diagnostic/Logging

Error safe position

Manual override

Minimum stroke setting

Mode, status and position indication

On-off control

Output signal VDC

Plus version: With optional BUS communication board. + ModBus or BACnet. With optional relay board. + 1 binary input, max. 100 Ω, cable max. 10 m or shielded. + 2 relays, max. 5A, 30 VDC/250 VAC on resistive load. + Output signal in mA

Proportional control

Stroke detection

Stroke limitation setting

Valve blockage protection

Valve clogging detection

Temperature

Media temperature: 32°F – +248°F

Operating environment: 32°F to 122°F (5-95%RH, non-condensing)

Storage environment: -4°F to 158°F (5-95%RH, non-condensing)

Control speed

76.2, 101.6, 152.4, 203.2, 304.8 or 406.4 s/in

Default setting: 76.2 s/in.

Supply voltage [V]

24 VAC/VDC ±15%., 100-240 VAC ±10%., Frequency 50/60 Hz ±3 Hz

Power consumption

Power consumption: 24 VAC/VDC:
Operation: 8 VA (VAC); 4.5 W (VDC)
Standby: 1 VA (VAC); 0.5 W (VDC)
100-240 VAC:
Operation: 9.7 VA (VAC)
Standby: 1.8 VA (VAC),

Input signal

0(2)-10 VDC, Ri 47 kΩ.

0(4)-20 mA R i 500 Ω.

Adjustable sensitivity 0.1-0.5 VDC; 0.33 Hz low pass filter.

Default setting: Proportional 0-10 VDC

Proportional dual-range (for change-over): 0-3.3 / 6.7-10 VDC, 10-6.7 / 3.3-0 VDC, 2-4.7 / 7.3-10 VDC or 10-7.3 / 4.7-2 VDC.

Proportional: 0-10, 10-0, 2-10 or 10-2 VDC; 0-20, 20-0, 4-20 or 20-4 mA

Proportional split-range: 0-5, 5-0, 5-10 or 10-5 VDC; 0-4.5, 4.5-0, 5.5-10 or 10-5.5 VDC; 2-6, 6-2, 6-10 or 10-6 VDC; 0-10, 10-0, 10-20 or 20-10 mA; 4-12, 12-4, 12-20 or 20-12 mA

Output signal

0(2)-10 VDC, max. 8 mA, min. 1.25 kΩ.

Default setting: Proportional 0-10 VDC

Plus version: 0(4)-20 mA, max. 700 Ω.

Ranges: See “Input signal”.

Stroke

0.87 in

Automatic detection of the valve lift (stroke detection)

Noise level

Max. 40 dBA

Marking

IMI TA, product name, article No. and technical specification.

LED indication description.

Colour

Orange RAL 2011, grey RAL 7043.

Adjusting force

168 lbf

Connection to valve

By two M8 screws to the valve and by quick connection to the stem

Cable

Wire cross-section*: 20 AWG-14 AWG (0.5-2.0 mm2)

- Protection class I: H05VV-F or similar

- Protection class III: LiYY or similar

*) Note: Wire cross-sections must be chosen according to actuator power consumption and line length, such as the voltage supply to the actuator does not go below 20.4 VAC/VDC (24 VAC/VDC minus 15%).

In case of VDC input signal on a 24 VAC/VDC powered actuator, the voltage drop on neutral line must be smaller than the defined hysteresis level for the VDC input signal.

Material

Cover: PBT

Bracket: Alu EN44200

Ingress protection

IP54 all directions (according to EN 60529)

Protection class

100-240 VAC: Class I.

24 VAC/VDC: Plus version with optional relay board, Class I.

(according to EN 61140)

All other versions, Class III safety extra low voltage.

Certifications and directives

EMC-D. 2014/30/EU: EN 60730-1, -2-14.

LV-D. 2014/35/EU: EN 60730-1, -2-14.

RoHS-D. 2011/65/EU: EN 63000