TA-Slider 750 Fail-safe T-2T
Digitally configurable proportional push-pull actuator with electronic fail-safe function and temperature measurement capability – 168 lbf (750 N)
Digitally configurable fail-safe actuators with temperature measurement capability for all control systems for all control systems with or without change-over. To be mounted on a PIBCV for tackling ΔT syndrome or for handling change-over based on T supply or ΔT sign detection. Wide range of setup possibilities gives high flexibility to adapt parameters on-site. Fully programmable binary input, relay and adjustable max. stroke of the valve bring new opportunities for advanced hydronic control and balancing.
Product branding

Features and Benefits
Functions
3-point control
Automatic change-over function
Delayed start-up
ΔT and temperature return limitation
Diagnostic/Logging
Electronic fail-safe function
Error safe position
Manual override
Minimum stroke setting
Mode, status and position indication
On-off control
Output signal VDC
Proportional control
Reading (supply/return temperature, ΔT, position)
Stroke detection
Stroke limitation setting
Valve blockage protection
Valve clogging detection
Temperature
Media temperature: 32°F – +248°F
Operating environment: 32°F to 122°F (5-95%RH, non-condensing)
Storage environment: -20°C – +50°C (5-95%RH, non-condensing)
Absolute temperature
Pt1000 Class AA: ±32.2 °F at 32 °F
Pt1000 Class B: ±32.5 °F at 32 °F
Control speed
76.2, 101.6, 152.4, 203.2, 304.8 or 406.4 s/in
Default setting: 76.2 s/in.
Supply voltage [V]
24 VAC/VDC ±15%. Frequency 50/60 Hz ±3 Hz
Power consumption
Input signal
0(2)-10 VDC, Ri 47 kΩ.
0(4)-20 mA R i 500 Ω.
Adjustable sensitivity 0.1-0.5 VDC; 0.33 Hz low pass filter.
Default setting: Proportional 0-10 VDC
Proportional dual-range (for change-over): 0-3.3 / 6.7-10 VDC, 10-6.7 / 3.3-0 VDC, 2-4.7 / 7.3-10 VDC or 10-7.3 / 4.7-2 VDC.
Proportional: 0-10, 10-0, 2-10 or 10-2 VDC; 0-20, 20-0, 4-20 or 20-4 mA
Proportional split-range: 0-5, 5-0, 5-10 or 10-5 VDC; 0-4.5, 4.5-0, 5.5-10 or 10-5.5 VDC; 2-6, 6-2, 6-10 or 10-6 VDC; 0-10, 10-0, 10-20 or 20-10 mA; 4-12, 12-4, 12-20 or 20-12 mA
Output signal
0(2)-10 VDC, max. 8 mA, min. 1.25 kΩ.
0(4)-20 mA, max. 700 Ω.
Default setting: Proportional 0-10 VDC
Ranges: See “Input signal”.
Characteristics
Default setting: Linear.
Linear, EQM 0.25 and inverted EQM 0.25.
Measurement accuracy
Time constant τ (63%)
In valve measuring point: 5s
Surface mounted: 20s
Temperature pocket: 9s
Stroke
0.87 in
Automatic detection of the valve lift (stroke detection)
Noise level
Max. 40 dBA
Marking
Colour
Orange RAL 2011, grey RAL 7043.
Adjusting force
168 lbf
Connection to valve
By two M8 screws to the valve and by quick connection to the stem
Temperature sensor cable
Halogen free, fire class IEC 60332-3-24 (cat. C).
Cable
Material
Ingress protection
IP54 all directions (according to EN 60529)
Protection class
(according to EN 61140)
Class I
Weight
3,5 lb
Certifications and directives
EMC-D. 2014/30/EU: EN 60730-1, -2-14.
LV-D. 2014/35/EU: EN 60730-1, -2-14.
RoHS-D. 2011/65/EU: EN 50581.