TA-Smart Fail-safe – NPT threads/ANSI flanges
2-way control valve with uniquely shaped EQM characteristics with flow, temperature, power measurement capabilities and electronic fail-safe function
The ultrasonic flow measurement technology combined with unique actuation algorithms capabilities provide best-in-class control performances. The TA-Smart Fail-safe controls can be set to flow or power, giving high on-site flexibility and providing highly effective comfort in heating and cooling applications. Its compact arrangement and simple set-up reduces installation and commissioning time.
Product branding

Features and Benefits
Applications
Heating and cooling systems.
Functions
Control (flow, power, position)
Pre-setting (max./min. flow, max. power, max./min. position)
Reading (flow, power, energy, supply/return temperature, ΔT, position)
Change-over
Delayed start-up
ΔT and temperature return limitation
Diagnostic/Logging
Electronic fail-safe function
Error safe position
Manual override
Mode, status and position indication
Valve blockage protection
Valve clogging detection
Wireless
Thread
Bluetooth Low Energy (BLE)
Pressure class [PN]
1/2" - 2": PN 25 (362 psi)
2 1/2" - 5": Class 150
Differential pressure (ΔpV)
Max. differential pressure (ΔpVmax): 400 kPa = 4 bar
Closing pressure: 600 kPa = 6 bar
ΔpVmax = The maximum allowed pressure drop over the valve to fulfill all stated performances.
Flow range
The flow ranges (qsetmin - qnom) for different dimensions:
1/2": 0.70 - 5.28 gpm
3/4": 1.67 - 8.37 gpm
1": 2.38 - 11.89 gpm
1 1/4": 4.05 - 20.2 gpm
1 1/2": 6.86 - 34.3 gpm
2": 11.8 - 59.0 gpm
2 1/2": 25.5 - 128 gpm
3": 38.0 - 190 gpm
4": 62.5 - 312 gpm
5": 98.6 - 493 gpm
Minimum controllable flows (qcontr.min) size 1/2" 0.33% of qnom, sizes 3/4" - 5" 0.5% of qnom.
qsetmin = Minimum settable flow.
qnom = Maximum settable flow.
Temperature
Max. working temperature: 110°C
Min. working temperature: 14°F
Operating environment: 32°F to 122°F (5-95%RH, non-condensing)
Storage environment: -4°F to 158°F (5-95%RH, non-condensing)
Media
Water or neutral fluids, water-glycol mixtures (0-57%).
Supply voltage [V]
24 VAC/VDC ±15%. Frequency 50/60 Hz ±3 Hz
Power consumption
Input signal
By BACnet/Modbus or Analog signal. Analog in VDC or mA, selectable by jumper in the SmartBox;
Proportional dual-range (for change-over): 0-4.5 / 5.5-10 VDC. 2-5.5 / 6.5-10 VDC. 0-3.3 / 6.7-10 VDC. 2-4.7 / 7.3-10 VDC. 0-9 / 11-20 mA. 4-11 / 13-20 mA.
0(2)-10 VDC, Ri 47 kΩ.
0(4)-20 mA R i 500 Ω.
Adjustable sensitivity 0.1-0.5 VDC; 0.33 Hz low pass filter.
Default setting: Proportional 0-10 VDC
Proportional: 0-10, 10-0, 2-10 or 10-2 VDC; 0-20, 20-0, 4-20 or 20-4 mA
Proportional split-range: 0-5, 5-0, 5-10 or 10-5 VDC; 0-4.5, 4.5-0, 5.5-10 or 10-5.5 VDC; 2-6, 6-2, 6-10 or 10-6 VDC; 0-10, 10-0, 10-20 or 20-10 mA; 4-12, 12-4, 12-20 or 20-12 mA
Output signal
0(2)-10 VDC, max. 8 mA, min. 1.25 kΩ.
BACnet/Modbus
Characteristics
Settable: Stepless between EQM 0.25 and inverted EQM 0.25.
Flow control accuracy
±10% from 0.5% to 4% of qnom
±5% from 4% to 100% of qnom
Measurement accuracy
Leakage rate
DN 15-50: Leakage rate < 0.01% of q, nom with correct flow direction (Class IV according to EN 60534-4)
DN 65-125: Tight sealing with correct flow direction (Class V according to EN 60534-4)
Pipe connection
1/2" - 2": External thread according to ISO 228. Connections (accessories) with internal NPT according to ANSI/ASME B1.20.1-1983, or for soldering according to ASME/ANSI B16.18.
2 1/2" - 5": Flanges according to ASME 7 ANSI B16.42 Class 150.
Temperature sensor cable
32.8 ft. halogen free cable on request.
1/2" - 2": 9.8 ft halogen free
2 1/2" - 5": 16.4 ft halogen free
Material
Surface treatment
1/2" - 2": Non treated
2 1/2" - 5": Electrophoretic painting
Ingress protection
IP54 (according to EN 60529)
Protection class
III (SELV)
(according to EN 61140)
Certifications and directives
EMC-D. 2014/30/EU: EN 60730-1, -2-14.
PED: 2014/68/EU
Product standards EN 60730-x.